Grid connected homebrew wind turbines

In response to a comment from Michael Jones I am posting a brief note about grid connection of homebrew wind turbines of my Recipe designs.

The turbine output voltage depends on both the rpm and number of turns in the coils.  It increases in exact proportion to both the number of turns and the speed of rotation.  For battery chargers we must wind coils that produce 12,24 or 48 volts at the desired blade rpm.  For grid connection we need to base our coil design on the input DC voltage range offered by the grid-connect inverter.

I do not recommend using a battery based system for grid connection in Europe (although you can do it with a ‘Sunny Island’ inverter).  In North America the Outback is worth looking at.  But think hard before you buy into a battery-based grid-tie system. It shares the worst features of both battery systems and grid systems.  The best way to connect to the grid is usually without batteries.

I have offered suggestions for turns per coil and wire sizes for grid connected turbines using WindyBoy inverters sizes on page 36 of the Recipe Book.  But I have never personally built a grid tied turbine on my own, because I live off-grid.  I do understand the principles well, and I have helped many others to do it successfully.  The people who have most hands on experience with work on my Recipe machines are Ti’eole in France.  See also this post if you are building a 4200 diameter turbine.

The main difference between a grid connected inverter (such as the Windy Boy or the Aurora) and a battery is that the inverter can accept a wide range of (often rather high) DC voltages that you can program in advance, whereas a battery works at a lower DC voltage that is arbitrarily fixed at a level that depends on its state of charge.  Often the relatively constant battery voltage is not the ideal level for the wind turbine to be producing power at over a wide range of different windspeeds.  It can be a bit like driving a car in the wrong gear.  It may struggle or stall.  With an inverter you can shift gears.

The exact input voltage of an inverter can be programmed as a function of Watts using interface software, such as the above SMA program.  Often this will be done by your supplier, but anyone can do it with a PC and a service cable.  The idea is to set a voltage level for each power level (windspeed) that will achieve the correct rpm in the alternator to load the blades at their best tip speed ratio.  I can offer help with choosing the best inverter settings based on your stator details.  I can also supply inverters, and arrange for programming.

Not only are the blades run at their best speed by the inverter, but the alternator can handle much higher peak power outputs compared with a battery charging alternator setup.  This is because the alternator now works over a range of voltages.  Wind turbines can only produce a relatively low voltage at low rpm, but the voltage naturally increases with speed so that the required current is relatively low in strong winds.

The downside of working at high and variable voltages is that the turbine becomes a significant hazard to the inverter and to humans.  If the inverter is not drawing current off the alternator then the blades will be unloaded and will overspeed, producing dangerously high voltages.  You will need a ‘voltage clamp’ or ‘protection box’ that connects the turbine to a heater when the voltage reaches a certain level where it threatens to damage the inverter.  The voltage clamp works very like a diversion load controller on a battery system.  It diverts current into heat, sufficient to prevent voltage rise above a set level.  It relies on a large bank of capacitors. The inverter probably provides the capacitors, and should also be kept connected for this reason.

Actually the protection box makes the wind turbine into a heating turbine that can also feed power to the grid.  You really need that heating controller as a backup, since the grid is not a reliable load.  But if all you wanted to do were to run heaters, you would probably choose a different setting on the heating control box so that it would come into action at lower voltage and run the blades more slowly.

Another additional safety option that makes sense to have is an over-voltage trip. This is a circuit that connects a big dump load (or even a short circuit) to the turbine if the voltage exceeds a given limit. In case the other circuits fail …

It’s wise the treat the wiring with respect too and makes sure there is good insulation and no chance of wires scuffing themselves on bare metal in the tower for example.  This is a lethal voltage source and there is no means to wire in protection against faults.

Other electronic equipment is available out there.  I have used Solar Converter’s LDR controllers for both nverter protection and for heating systems.  Smaller systems are often based on Windmaster 500 inverters working at 50-100 volts.

 

 

About hugh

I live off-grid in NW Scotland and have spent my life playing with wind turbines. I also love small hydros. Hands on renewable energy is my thing and I like to learn and to share my experiences.
This entry was posted in construction, products/technical, wind systems tutorial. Bookmark the permalink.

13 Responses to Grid connected homebrew wind turbines

  1. Could Olivier says:

    Hi Hugh,
    I’m almost ready to connect my 2,4m 24V turbine to the grid. I bought a SMA Windy Boy 1100LV, the Set Up software needs an “installer” password to modify settings (the previous owner changed the settings for an experimental water turbine). I asked it to SMA France service but they no longer support Wind products…
    Have you got this special password ?
    Have you got the specific curve to set in the windy boy (24V 700W 2,4m turbine) ?

    Thanks

    Olivier

  2. John de Rivaz says:

    Anyone here got a circuit diagram for the Proven voltage controller for a 2007 6kWp grid connect turbine?
    New controllers cost thousands (+VAT) but the components are quite cheap.
    The usual culprits are the diodes (rectifier and zener) but if the circuit board gets burned it is difficult to see where the tracks went.
    I am told that burnouts are not uncommon. Maybe a three phase trip after the feed from the turbine would be a good idea.

    • hugh says:

      hi John,

      I am more of an off-grid person and know a limited amount about this stuff but if you need help I can recommend Quentin at Voltsys in Ireland. https://www.voltsys.com/

      Likely the inverter that was used back in 2007 is no longer available nor the other electronics which may easily have needed some improvements anyway. There is a fair chance that there will be secondhand units around the county here and there though. Maybe ask Mike Field at naturalgen.co.uk

      cheers
      Hugh

  3. Hans Zurne says:

    Hi Hugh
    I have a3 kw 220 volt chinese turbine , I never got it working real good
    now I bought a ginlong 5 kw grit tied inverter and i have to put in the power curve , do You know , what this power curve should be
    the controler starts dump load at 300 volt
    i realy could do with some help here
    thanks
    Hans New Zealand

    • admin says:

      hi Hans
      there is no simple answer and you may need to use some trial and error. If the voltage is too low (for a given power) then you may stall the turbine so it is very quiet but does not achieve much. If the voltage is too high then it will run fast and noisy without a good output. You need to find the sweet spot between the two.

      Likely you will want to cut in around 100V and ramp it up to 250 volts for 3kW power. The curve should be hooked upward so maybe try 1kW at 200V, 200W at 150V or something like that.

      cheers
      Hugh

  4. Rufus maurice says:

    Hi Hugh,
    I appreciate all you are doing to promote ,encourage and champion wind energy in a pratical way.
    I almost built one of your turbines when a friend spotted a 2nd hand evance r9000 on ebay. It came with 2 windy boys a rectifier the tower and a load of cable.
    I to am off grid and have connected to a sunny island .i set the system up last january and it has worked well apart from the turbine ‘pitch’s’ its blades when the speed increases (a useful safety mechanism but it has the effect of stalling the turbine ).so i started to investigate voltage controlled ‘dump loads ‘and came across the windy boy protection box which looks like what I need . unfortunately when I contacted Steve at wind and sun he told me that S.M.A have gone out of wind energy and no longer sell w.b.p.boxes .do you know what I could do instead? Still a fan of cheap and agricultural if well built!
    many thanks rufus (cornwall)

    • admin says:

      hi Rufus,

      If you need a voltage controlled heating load to limit the rise in voltage on the wind turbine when the battery is full then maybe try 2V microsystems. http://www.powerpal.co.uk/ppelec.html
      Or there ought to be ways to divert the energy before the sunny island raises the frequency and dumps the windy boys. You could for example use a relay driver to control useful diversion loads based on battery voltage, or in some sunny islands there is even an internal relay setting for this.
      Wind and sun sell a device for operating diversion loads based on rising frequency called an amber switch
      http://ambercontrol.com/index.php/amber-switch that could maybe put a load on before the windy boys start to moderate the wind input.
      Lots of fun options!
      Hugh

  5. Michael O Connor says:

    How much does the windy boy and the windy boy protection box cost?

  6. Roger Brown says:

    what is your recommendation for the best battery manufacturer?

  7. admin says:

    Hi Dave,

    I am sorry but I don’t sell inverters in north america. I can sell them in Europe but I like to be able to offer good support and am really too busy to take on selling them that far away. Maybe try to find a more local supplier who has a good understanding of the product. I am happy as always to help with suggestions for settings etc.

    have fun

    Hugh

  8. Dave Agla says:

    Hello Hugh
    This is the first time that I have been on your blog. I have contacted you about building 2 turbines and if I should use 1 large or 2 small inverters. Am I correct in understanding that you handle Windyboy Inverters and Protection Boxes as well as programming them? I am going to build your 14′ turbine using the specification that are in your manual that I got from Craig and Connie Cook in Tillsonburg. These inverters seem to be well manufactured from what I have been able to find out. If you sell these units, do you have pricing available.

    Thanks
    Dave Agla